Installation Guidelines for Non-Metallic-Sheathed Cable ...

    https://www.cityofpensacola.com/DocumentCenter/View/100/Installation-Guidelines-for-Non-Metallic-Sheathed-Cable-Romex-PDF?bidId=
    Installation Guidelines for Non-Metallic-Sheathed Cable (Romex) Note: Number 14 is missing a number 1. Bored holes MUST BE 1 1/4 inch from the edges of any stud or top plate. NEC sec. 300-4A-1 2. Notches in studs REQUIRE nail plates. NEC sec 300.4A-2 3. Cable MUST BE stapled at least 1 1/4 inch from the edge of studs. NEC sec. 300-4B-2 4.

NMC (ROMEX) SUPPORT AND SECURE Mike Holt's Forum

    https://forums.mikeholt.com/threads/nmc-romex-support-and-secure.149479/
    May 10, 2019 · 334.30 States that the romex is required to be supported and secured every 4.5' min. In an attic where it is accessible, this is the method we use. A house that has a flat roof and second floor. The entire attic is NOT accessible.

Attaching Electrical Cables to Framing Members

    https://www.thespruce.com/securing-electrical-cables-1152891
    Most of the wiring in a modern home consists of runs of nonmetallic sheathed cable, or NM cable (also known by the popular brand name Romex). NM cable must be supported by framing when running through walls, ceilings, and floors. The National Electrical Code  (NEC) outlines specifications for securing NM cable and other electrical wiring.

NMC (ROMEX) SUPPORT AND SECURE - Mike Holt's Forum

    https://forums.mikeholt.com/forum/active-forums/general-electrical-forum/149479-nmc-romex-support-and-secure
    NMC (ROMEX) SUPPORT AND SECURE 05-09-19, 12:45 PM 334.30 States that the romex is required to be supported and secured every 4.5' min. In an attic where it is accessible, this is the method we use.

2011 NEC Revisions for Cable EC&M

    https://www.ecmweb.com/national-electrical-code/code-basics/article/20896213/2011-nec-revisions-for-cable
    Where are the NEC requirements for the various types of cables you might use? You’ll find those in Chapter 3 — Articles 320 through 340. These sections of the Code focus on armored cable, flat cable assemblies, flat conductor cable, integrated gas spacer cable, medium-voltage cable, metal-clad cable, mineral-insulated metal-sheathed cable, nonmetallic-sheathed cable, power and control ...

Supporting Romex with Romex - ECN Electrical Forums

    https://www.electrical-contractor.net/forums/ubbthreads.php/topics/109781/all/Supporting_Romex_with_Romex.html
    Mar 13, 2010 · 334.30 Securing and Supporting. Nonmetallic-sheathed cable shall be secured by staples, cable ties, straps, hangers, or similar fittings designed and installed so as not to damage the cable at intervals not exceeding 1.4 m (41/2 ft) and within 300 mm (12 in.) of every cabinet, box, or fitting. Flat cables shall not be stapled on edge.

National Electrical Code Top Ten Tips: Article 300, Wiring ...

    http://www.codebookcity.com/codearticles/nec/necarticle300.htm
    Many folks who run nonmetallic-sheathed cables (e.g., Romex) don’t consider adding protection. In residential applications, this is usually unnecessary, but a hole drilled off-center could easily leave the wiring susceptible to puncture from a nail or screw driven to support shelving, cabinets, or other wall-mounted objects.

Do I really have to fasten interior-wall electrical wire ...

    https://diy.stackexchange.com/questions/11617/do-i-really-have-to-fasten-interior-wall-electrical-wire-to-a-stud-to-keep-it-fr
    In other than vertical runs, cables installed in accordance with 300.4 shall be considered to be supported and secured where such support does not exceed 1.4-m (4 1⁄2-ft) intervals and the nonmetallic-sheathed cable is securely fastened in place by an approved means within 300 mm (12 in.) of each box, cabinet, conduit body, or other nonmetallicsheathed cable termination.

9 Common Wiring Mistakes and Code Violations

    https://www.finehomebuilding.com/membership/pdf/20751/021190076.pdf
    Romex needs its jacket whole On more than one occasion, I have seen wires ... the NEC Handbook, which has a section dedicated to this subject; you also can read ... carrying wires are meant to support only their own weight. If a lot of wires are already hanging from the bottom of the floor joists, you can run

NEC Requirements

    http://www.cooperindustries.com/content/dam/public/bline/Resources/Library/catalogs/fasteners_and_fixing/spring_steel_fasteners_NA/NECRequirements.pdf
    in place. Support wires that do not provide secure support shall not be permitted as the sole support. Support wires and associated fittings that provide secure support and that are installed in addition to the ceiling grid support wires shall be permitted as the sole support. Where independent support …