Fastening shall be permitted to be increased to a distance of 1.5 m (5 ft) where structural members do not readily permit fastening within 900 mm (3 ft). Where approved, conduit shall not be required to be securely fastened within 900 mm (3 ft) of the service head for above-the-roof termination of a mast.
https://www.engineeringtoolbox.com/piping-support-d_362.html
Epoxy Pipes - Support Spacing - Support spacing for reinforced Epoxy fiberglass pipes; Piping Elbows - Thrust Block Forces - Thrust block forces on pipe bends anchor due to liquid velocity and internal pressure - online resulting force calculator; PP Pipes - Support Spacing - Maximum distance between PolyPropylene pipes supports
https://www.engineeringtoolbox.com/support-space-pvc-pipes-d_790.html
PP Pipes - Support Spacing - Maximum distance between PolyPropylene pipes supports Pressfit Pipes - Supports - Maximum distance between pressfit pipe supports PVC - Friction Loss in Fittings and Equivalent Length - Minor loss in PVC and CPVC fittings as equivalent length of straight pipe
http://www.piping-engineering.com/minimum-pipe-spacing-chart.html
To Determine spacing between 150 NB Pipe 150# flange rating and a 100 NB pipe With 600# flange rating. For 150 NB pipe and 100NB 600# flange Rating spacing = 255mm. For 100 NB pipe and 150 NB150# flange Rating spacing =230mm. Consider the maximum distances from 2 cases.
https://www.ecmweb.com/cee-news-magazine-archive/article/20894958/code-guide
Generally, the maximum support spacing requirement for RMC (rigid metallic conduit) of trade size 1 is 10 ft, but for straight runs with threaded couplings, this spacing is increased to 12 ft. Nothing in the NEC states that you cannot use the same supports for conduit as for other systems.
http://wiresizecalculator.net/tables/conduitsupportstable.htm
Conduit Size Distance Between Supports; ½" - ¾" 10 Feet: 1" 12 Feet: 1¼" - 1½" 14 Feet: 2" - 2½" 16 Feet: 3" and larger: 20 Feet
https://www.enggcyclopedia.com/2012/06/spacing-pipe-supports/
For example, for copper tubing, support spacing varies from 8-ft for 1" tubing to 12-ft for 4". For PVC pipe the spacing depends on the pipe schedule and operating temperature. The span is 4-ft for %" pipe up to 6-ft for 4" schedule 40 pipe at ambient temperature; approximately 1-ft more for schedule 80,...
https://www.eng-tips.com/viewthread.cfm?qid=49424
Nov 22, 2005 · The best rule of thumb for hanger spacing for pipe is the pipe diameter in feet plus 10. Example: a 3" pipe would require a support every 3'+10" = 13'-0. Use that and you should be fine for small diameter pipes 1/2" - 12".
https://www.guenthersupply.com/pdf/hanger-spacing-weight-chart.pdf
* Many codes require pipe hangers to be spaced every 10 ft. regardless of 1 Cubic Ft. of water weighs 62.41 lbs. size. Check local codes. 1 gallon (U.S.) weighs 8.335 lbs. Spacing and capacities are based on water filled pipe. Closer hanger spacing may be required where additional valves and fittings increase the load.
https://steeltubeinstitute.org/steel-conduit/wp-content/uploads/sites/4/2013/04/ConGuide.pdf
Conduit joint The coupling of two pieces of conduit or tubing, or coupling a length of conduit or tubing to a bend. NOTE: One of the most important elements of an electrical installation. Coupling, integral A coupling meeting the requirements of UL 514B which is assembled to the conduit, tubing, or elbow during manufacture and is not readily removable.