https://www.engineeringtoolbox.com/piping-support-d_362.html
Hangers - Support Spacing and Rod Size for Horizontal Pipes. Recommended maximum support span between hangers - and rod sizes for straight horizontal pipes. Recommended maximum space between hangers for straight horizontal pipes and tubes are indicated in the table below.
http://www.inertance.com/engineering-calculator/span/
The piping support span length should be determined to avoid any coincidence of excitation frequencies with mechanical natural frequencies of the compressor, pump and piping system. The minimum mechanical natural frequency of piping system element shall be designed to be greater than 2.4 times maximum rated speed of equipment.
http://pipingdesigners.com/images/Downloads/pipe_span_chart.xls
Hydrostatic testing: Spans are adequate without the addition of auxiliary supports for insulated lines and lines on shoes. specified in the above table. Corrosion Allowance: As indicated, spans can be used for lines of equivalent or smaller allowance than those Nominal Pipe Size 40.00 1.27 3.50 40.00 1.27 40.00 1.27 5.50 40.00 2.54 5.50 40.00 2.54 40.00 2.54 40.00
https://www.whatispiping.com/pipe-support-span
Pipe Support Span (Fig. 1) is defined as the optimum distance between two supports so as to avoid excessive sagging. Pipe span varies with changes inAuthor: Anup Dey
http://www.wermac.org/steel/pipesupports_spacing.html
Determination of maximum allowable spacing, or span between supports, is based on the maximum amount that the pipeline may deflect due to load. Typically, a deflection of 2.5 mm is allowed, provided that the maximum pipe stress is limited to 1,500 psi or …
http://piping-designer.com/index.php/datasheets/piping-layout-information/1669-allowable-pipe-span
Spans are based on using carbon steel pipe (A53-GR.B) filled with water. Spans are based on 12 1/2% mill tolerance and .065" correction tolerance. Spans are based on insulated and uninsulated lines below 650°F. If supports are spaced greater than 25'-0" consultation with a structural engineer should be performed for additional analysis.
https://www.commercial-industrial-supply.com/resource-center/pvc-pipe-support-spacing-guide/
You’ll find that your support needs vary from system to system based on configuration, pipe size, load, and temperature. There are also other things to keep in mind when planning your support. Valves and other points of extra load should be supported separately from your pipe spacing.
https://www.guenthersupply.com/pdf/hanger-spacing-weight-chart.pdf
PIPE HANGER SPACING & WEIGHT CHART Phone: 920-921-0821 Toll Free: 1-800-236-1458 Fax: 920-921-5409 Web: www.guenthersupply.com SCHEDULE 40 STEEL PIPE DATA Nominal Wall Weight of Pipe Suggested Recommended Pipe Size Pipe O.D. Thickness Weight of Pipe Filled with Water Maximum Span* Hanger Rod Sizes In. In. In. Lbs/Ft. Lbs.Ft. Ft. Sizes
http://www.wermac.org/pdf/steel3.pdf
(Since the pipe is not considered to carry flanges, it will not carry any concentrated load; hence 2nd element of equation is eliminated) Maximum Span between supports is calculated as 11.38 meters, which is rounded back to 11.0 meters. Hence number of supports required for 15 km pipeline is approx.